如何判斷電纜橋架的故障?
1、故障的測(cè)試方法過去使用的儀器設(shè)備有QF1-A型電纜探測(cè)儀、DLG-1型閃測(cè)儀,路徑儀及故障定點(diǎn)儀等。在20世紀(jì)70年代以前,廣泛使用的電纜故障測(cè)試方法是電橋法,包括電阻電橋法、電容電橋法、高壓電橋法。這種測(cè)試方法誤差較大,對(duì)某些類型的故障無(wú)法測(cè)量,所以目前非常流行測(cè)試方法是閃測(cè)法,它包括沖閃和直閃,常用的是沖閃法。沖閃測(cè)試精度較高,操作簡(jiǎn)單。其設(shè)備主要由兩部分組成,即高壓發(fā)生裝置和電流脈沖儀。高壓發(fā)生裝置是用來(lái)產(chǎn)生直流高壓或沖擊高壓,施加于故障電纜上,迫使故障點(diǎn)放電而產(chǎn)生反射信號(hào)。電流脈沖儀是用來(lái)拾取反射信號(hào)測(cè)量故障距離或直接用低壓脈沖測(cè)量開路、短路或低阻故障。
1. Fault test methods in the past, the instruments and equipment used were qf1-a cable detector, Dlg-1 flash tester, Pathfinder and fault locator. Before the 1970s, the widely used cable fault test method was the electric bridge method, including resistance bridge method, capacitance bridge method and high voltage bridge method. This test method has large error and can not measure some types of faults. Therefore, at present, the very popular test method is flash method, which includes flash and direct flash, and the commonly used flash method is flash method. The flash test has high precision and simple operation. The equipment is mainly composed of two parts: high voltage generator and current pulse meter. The high voltage generator is used to generate DC high voltage or impulse high voltage, which is applied to the fault cable to force the fault point to discharge and generate reflected signal. The current pulse meter is used to pick up the reflected signal to measure the fault distance or directly measure the open circuit, short circuit or low resistance fault with low-voltage pulse.
下面以故障點(diǎn)電阻為依據(jù)簡(jiǎn)述一下測(cè)試方法:
The following is a brief description of the test method based on the fault point resistance:
(1)當(dāng)故障點(diǎn)電阻等于無(wú)窮大時(shí),用低壓脈沖法測(cè)量容易找到斷路故障,一般來(lái)說,純粹性斷路故障不常見到,通常斷路故障為相對(duì)地或相間高阻故障或者相對(duì)地或相間低阻故障并存。(2)當(dāng)故障點(diǎn)電阻等于零時(shí),用低壓脈沖法測(cè)量短路故障容易找到,但實(shí)際工作中遇到這種故障很少。(3)當(dāng)故障點(diǎn)電阻大于零小于100Ω時(shí),用低壓脈沖法測(cè)量容易找到低阻故障。(4)閃絡(luò)故障可用直閃法測(cè)量,這種故障一般存在于接頭內(nèi)部,故障點(diǎn)電阻大于100Ω,但數(shù)值變化較大,每次測(cè)量不確定。(5)高阻故障可用沖閃法測(cè)量,故障點(diǎn)電阻大于100Ω且數(shù)值確定。一般當(dāng)測(cè)試電流大于15mA,測(cè)試波形具有重復(fù)性以及可以相重疊,同時(shí)一個(gè)波形有一個(gè)發(fā)射、三個(gè)反射且脈沖幅度逐漸減弱時(shí),所測(cè)的距離為故障點(diǎn)到測(cè)試端的距離;否則為故障點(diǎn)到電纜測(cè)試對(duì)端的距離。
(1) When the resistance at the fault point is equal to infinity, it is easy to find the open circuit fault by measuring with the low-voltage pulse method. Generally speaking, pure open circuit fault is not often seen. Usually, the open circuit fault is a phase to ground or phase to phase high resistance fault or the coexistence of phase to ground or phase to phase low resistance fault. (2) When the resistance at the fault point is equal to zero, the short-circuit fault measured by low-voltage pulse method is easy to find, but this fault is rarely encountered in practical work. (3) When the resistance at the fault point is greater than zero and less than 100 Ω, it is easy to find the low resistance fault by measuring with low voltage pulse method. (4) The flashover fault can be measured by direct flashover method. This fault generally exists in the connector. The resistance at the fault point is greater than 100 Ω, but the value changes greatly, and each measurement is uncertain. (5) High resistance fault can be measured by impulse flashover method. The resistance at the fault point is greater than 100 Ω and the value is determined. Generally, when the test current is greater than 15mA, the test waveform has repeatability and can overlap, and one waveform has one emission and three reflections, and the pulse amplitude gradually decreases, the measured distance is the distance from the fault point to the test end; Otherwise, it is the distance from the fault point to the opposite end of the cable test.
2、結(jié)束語(yǔ)電纜故障測(cè)試技術(shù)水平的提高,應(yīng)針對(duì)不同的故障性質(zhì)采取不同的方法,還要不斷引進(jìn)新技術(shù)、新設(shè)備,同時(shí)也要在新設(shè)備上摸索經(jīng)驗(yàn),開發(fā)新的功能。如現(xiàn)采用的發(fā)音頻信號(hào)給電纜,在故障點(diǎn)接收信號(hào)的測(cè)試技術(shù),以及利用T16/910電纜故障測(cè)試儀的SDC系列高智能電纜故障閃測(cè)儀對(duì)故障點(diǎn)的準(zhǔn)確定位。這些設(shè)備可以使其測(cè)量誤差控制在幾十厘米以內(nèi),直接找到故障點(diǎn)進(jìn)行處理,提高了故障測(cè)尋的效率。
2. Conclusion to improve the technical level of cable fault testing, we should adopt different methods according to different fault properties, and constantly introduce new technologies and equipment. At the same time, we should also explore experience and develop new functions on new equipment. For example, the test technology of using the pronunciation frequency signal to the cable and receiving the signal at the fault point, as well as the accurate positioning of the fault point by using the SDC series high intelligent cable fault flash tester of T16 / 910 cable fault tester. These devices can control the measurement error within tens of centimeters, directly find the fault point for processing, and improve the efficiency of fault detection.
3、故障的類型電力電纜由于機(jī)械損傷、絕緣老化、施工質(zhì)量低、過電壓、絕緣油流失等都會(huì)發(fā)生故障。根據(jù)故障性質(zhì)可分為低電阻接地或短路故障、高電阻接地或短路故障、斷線故障、斷線并接地故障和閃絡(luò)性故障。
3. Type of fault power cable will fail due to mechanical damage, insulation aging, low construction quality, overvoltage, loss of insulating oil, etc. According to the nature of the fault, it can be divided into low resistance grounding or short circuit fault, high resistance grounding or short circuit fault, wire break fault, wire break and grounding fault and flashover fault.
4、故障的判斷方法確定電纜故障類型的方法是用兆歐表在線路一端測(cè)量各相的絕緣電阻。一般根據(jù)以下情況確定故障類型:(1)當(dāng)搖測(cè)電纜一芯或幾芯對(duì)地絕緣電阻,或芯與芯之間絕緣電阻低于100Ω時(shí),為低電阻接地或短路故障。(2)當(dāng)搖測(cè)電纜一芯或幾芯對(duì)地絕緣電阻,或芯與芯之間絕緣電阻低于正常值很多,但高于100Ω時(shí),為高電阻接地故障。(3)當(dāng)搖測(cè)電纜一芯或幾芯對(duì)地絕緣電阻較高或正常,應(yīng)進(jìn)行導(dǎo)體連續(xù)性試驗(yàn),檢查南京橋架是否有斷線,若有即為斷線故障。(4)當(dāng)搖測(cè)電纜有一芯或幾芯導(dǎo)體不連續(xù),且經(jīng)電阻接地時(shí),為斷線并接地故障。(5)閃絡(luò)性故障多發(fā)生于預(yù)防性耐壓試驗(yàn),發(fā)生部位大多在電纜終端和中間接頭。閃絡(luò)有時(shí)會(huì)連續(xù)多次發(fā)生,每次間隔幾秒幾分鐘。
4. The method to determine the type of cable fault is to measure the insulation resistance of each phase at one end of the line with a megger. The fault type is generally determined according to the following conditions: (1) when the insulation resistance of one or several cores of the cable to the ground is measured by shaking, or the insulation resistance between cores is less than 100 Ω, it is a low resistance grounding or short-circuit fault. (2) When the insulation resistance of one or several cores of the cable to the ground is measured by shaking, or the insulation resistance between cores is much lower than the normal value but higher than 100 Ω, it is a high resistance grounding fault. (3) When the insulation resistance of one or more cores of the telemetry cable to the ground is high or normal, a conductor continuity test shall be carried out to check whether there is a wire break in Nanjing bridge. If so, it is a wire break fault. (4) When one or more core conductors of the telemetry cable are discontinuous and grounded through resistance, it is a broken wire and grounding fault. (5) Flashover faults often occur in preventive voltage withstand tests, mostly at cable terminals and intermediate joints. Flashover sometimes occurs several times in a row, with an interval of a few seconds to a few minutes.